Automatic fire alarm system installation and acceptance of (the) – Automatic Fire Alarm, standard – by jojo

Standard number: GB50166-2007 Release Date: October 23, 2007 Implementation date: March 1, 2008 Issued by: The People’s Republic of China Ministry of Construction / HHH General Administration of Quality Supervision, Inspection and Quarantine (joint release)

Publisher: China plans Press Abstract: “Automatic fire alarm system installation and acceptance of” the formulation, not only for the installation, use and other departments and units provide a more scientific and rational unified national technical standards, fire protection for the public security and provides a basis for supervision and management of technology . This is a better play to the security of automatic fire alarm system, fire prevention work in an important role in preventing and reducing fire hazards, to protect personal and property safety and security of the socialist modernization drive, will have great significance. This specification is divided into six chapters, which also first 1.0.3,2.1.5,2.1.8,2.2.1,2.2.2,3.2.4,5.1.1,5.1.3,5.1.4,5.1.5 , for the mandatory provisions of Article 5.1.7, be strictly enforced. The original “automatic fire alarm system installation and acceptance of” GB50166-92 shall be repealed simultaneously.

Introduction This specification is based on the Ministry of Construction of Building Standards [1999] the requirements of article No. 15, Ministry of Public Security of Shenyang, together with the relevant units of the original national standard “fire alarm system installation and acceptance of” GB50166-92 comprehensive revision compiled on the basis of. In the specification revision process, the preparation of group follow the relevant laws, regulations and technical standards, carried out extensive research, carefully summed up the construction of China’s acceptance of automatic fire alarm system of practical experience, to seek the design, supervision, construction, products manufacture, fire supervision, and other comments about units, reference to relevant standards at home and abroad, and finally finalized by the expert review by the departments concerned. The code revision is mainly reflected in practical application problems, supplement and perfect the system parts of the equipment installation, commissioning, acceptance and other relevant technical content, an increase of sample aspirated through the pipeline Smoke Detector The construction and acceptance requirements, revised and “automatic fire alarm system design” GB50116-98 are inconsistent, incompatible technical content, the original standard system running a rewrite of the system use and maintenance, to enhance the system’s maintenance and use, and standardize the content from the format to prepare a comprehensive amended to further clarify the construction, construction units in construction and acceptance of the job duties, work procedures, to add modify the construction and acceptance of work required to complete various forms.

Bold logo of this specification to the provisions of the mandatory provisions must be strictly enforced.

1, General Provisions 1.0.1 In order to protect the automatic fire alarm system, construction quality and function, to prevent and reduce fire hazards, to protect personal and property safety, development of this specification.

1.0.2 This standard applies to industrial and civil buildings set automatic fire alarm system installation and acceptance. Does not apply to gunpowder, explosives, ammunition, pyrotechnics and other production and storage sites set up automatic fire alarm system installation and acceptance.

1.0.3 automatic fire alarm system must be delivered prior to acceptance.
1.0.4 automatic fire alarm system installation and acceptance, in addition to the implementation of the norms, there should be consistent with existing relevant national standards, norms.

2, the basic requirement 2.1 Quality Management 2.1.1 Division of automatic fire alarm systems, sub-divisions, sub-project Appendix A shall be divided.

2.1.2 Construction of automatic fire alarm systems must have the appropriate level of qualification by the construction unit.

2.1.3 Construction of automatic fire alarm system design requirements should be the preparation of construction programs. Construction site should have the necessary technical standards for construction, sound quality management system construction and engineering quality inspection system, and Appendix B, should be asked to fill in the record.

2.1.4 before the construction of automatic fire alarm system shall meet the following conditions:

1 design units shall construction, construction, supervision units clear the corresponding technical requirements;
2 system equipment, materials and accessories are complete and to ensure normal construction;
3 construction site and construction of the use of water, electricity, gas and construction should meet the normal requirements.

2.1.5 the construction of automatic fire alarm system shall be in accordance with the approved engineering design documents and construction technical standards for construction. Not free to change. Really necessary to change the design, the original design unit is responsible for change.

2.1.6 automatic fire alarm system, quality control during construction shall meet the following requirements:

1 The construction technology should be standard procedure for quality control, and each procedure is completed, should be inspected, after passing the examination before entering the next process.

2 related transfer between the various professional types, should be inspected by the supervising engineer visa before entering the next process.

3 system installation is complete, the construction unit should carry out the provisions of relevant professional debugging debugging.

4 system testing is completed, the construction unit construction unit shall submit quality control data and various types of construction quality inspection records.

5 construction quality inspection unit by the staff of construction supervision engineers to complete.
6 construction quality inspection records should be asked to fill in Annex C,.
2.1.7 Quality control of automatic fire alarm system information requirements should be completed in Appendix D.

2.1.8 before the construction of automatic fire alarm system, response equipment, materials and accessories for on-site inspections, check failure may not use.

2.1.9 Segment Acceptance by the quality of the project construction unit project leader project manager of construction units, supervision engineers and design unit

Project leader, etc., in accordance with the requirements of this standard in Appendix E automatic fire alarm system acceptance complete record.

2.2 equipment, materials testing approach
2.2.1 equipment, materials and accessories to the construction site should have a list of instructions, quality certification next document, the State quality inspection bodies of statutory inspection reports and other documents. Automatic fire alarm system in the compulsory certification (accreditation) Product should have the certification (approval) certificate and certification (accreditation) logo.

Check the quantity: full inspection. Test method: screening of related materials.
2.2.2 The main fire alarm system equipment shall be through the National Certification (approval) of the product. Product names, models, specifications and inspection reports should be consistent.

Check the quantity: full inspection. Test method: check certification (accreditation) certificate, inspection reports and products.

2.2.3 Automatic Fire Alarm System

I am a professional editor from Chinese Manufacturers, and my work is to promote a free online trade platform. http://www.chinaqualitycrafts.com/ contain a great deal of information about desk pad calendars ,

Article Source: http://www.earticlesonline.com/Article/Automatic-fire-alarm-system-installation-and-acceptance-of–the—-Automatic-Fire-Alarm–standard—/793452

No comments yet.